Lightning protection inspection report
Sample layout · Inspection to IEC 62305-3 (Annex E) and NF C 17-102
SAMPLE: this page shows the layout and the checks in our report. It contains no real site data. Each real report is filled in on site and signed by the inspecting technician.
1. Site and system
| Client and site | Inspection date | ||
|---|---|---|---|
| District | Inspected by | ||
| System type | ESE / conventional | Protection level | I / II / III / IV |
| Installed by / year | Last inspection | ||
| Type of inspection | Visual / complete / after a strike | ||
2. Checks
| Item | OK | Defect | Notes |
|---|---|---|---|
| Air terminal: condition, fixing, height above the highest point | |||
| Remote ESE status (where fitted) | |||
| Mast, guy wires and fixings | |||
| Down conductors: route, fixings, damage, corrosion | |||
| Test joints: condition and access | |||
| Mechanical protection up to 2 m | |||
| Strike counter reading (previous / now) | |||
| Inspection pits and earth electrodes | |||
| Equipotential bonding to the main earthing terminal | |||
| Surge protective devices: status indicators, connections | |||
| Changes to the building since the last inspection (new roof equipment, extensions, antennas, solar panels) | |||
| Danger signs in place and legible |
3. Measurements
| Earth termination / pit | Earth resistance (Ω), test joint open | Continuity (Ω) | Within limit? |
|---|---|---|---|
| Pit 1 | |||
| Pit 2 | |||
| Pit 3 | |||
| Global earth (all joints closed) |
Target: 10 Ω or less for each earth termination (NF C 17-102 and IEC 62305-3). Instrument used, serial number and calibration date are recorded on each real report.
4. Photos
Air terminalDown conductor and test jointInspection pitStrike counterSPD in main boardDefects found
5. Findings and recommendations
| Priority | Finding | Recommended action |
|---|---|---|
| Urgent | ||
| Within 3 months | ||
| At next inspection |
6. Conclusion and next inspection
| System condition | Satisfactory / satisfactory after repairs / not satisfactory | ||
|---|---|---|---|
| Next inspection due | Technician signature | ||
| Client representative | Signature and date | ||