Where the risk comes from
Risk components without protection (IEC 62305-2)
Free tool · Lightning protection
Work out the lightning risk for your building with the IEC 62305-2 method, the protection level it needs, and a complete ESE or mesh design with earthing, surge protection and a bill of materials.
3 · Design
Change the building or site details above and the design updates.
Risk components without protection (IEC 62305-2)
A mesh suits flat roofs and long buildings. An ESE system needs less conductor on the roof and is quicker to install on pitched and iron-sheet roofs.
Every earth is bonded to the building's main earth, fitted with a test joint and an inspection pit, and measured on handover.
4 · Materials
Quantities for budgeting. Final quantities come from the site survey and roof drawings.
| Item | Specification | Qty |
|---|
This tool gives an engineering estimate using simplified IEC 62305-2 risk components (R1: RA, RB, RC, RM, RU, RV, RW, RZ), NF C 17-102 protection radii and IEC 62305-3 mesh rules. It is not a certified design. Lightning density values for Rwanda are typical estimates. A site survey, soil resistivity test and inspection of the incoming services are needed before installation.
Questions
It estimates R1, the risk of loss of human life, following the method of IEC 62305-2. It combines the expected number of lightning strikes to the building and to its incoming power and telecom lines with the probability and consequences of injury, fire and failure of critical systems, and compares the result with the tolerable risk of 1 in 100,000 per year.
It tests protection levels IV, III, II and I, each with matching surge protection, and selects the lowest level that brings the risk below the tolerable value. If even Level I is not enough, it adds enhanced surge protection and flags the building for a detailed design.
The protection radius follows NF C 17-102: Rp = √(2rh − h² + ΔL(2r + ΔL)), where h is the height of the terminal above the roof, r depends on the protection level (20, 30, 45 or 60 m) and ΔL is the terminal's early streamer advance in metres. The tool finds the smallest number of terminals, the lowest ΔT and the shortest mast that cover the whole roof.
Rwanda has some of the highest lightning activity in the world, especially in the west and north and around Lake Kivu. The regional values in the tool are typical estimates for planning. If you have a measured ground flash density for your site, enter it instead.
No. It is a detailed first estimate to help you plan, budget and compare options. A certified design requires a site survey: we check the roof, the structure, the soil resistivity and the incoming services, then issue the design, drawings and test report.